8.4. Kentix Power-Adapter (KIO3) with digital I/O clips
The Kentix I/O Power-Adapter is used to expand your Kentix-solution to include the additional functions:
• Power supply for up to two MultiSensors-RF via an AC adapter
• Connecting of up to two external alarms via dry contacts to a MultiSensor
• Controlling resp. switching of up to two external devices via relays by a MultiSensor
#
The adapter is connected directly to the Kentix system jack and offers the possibility to power the
MultiSensor with a power plug or a permanently connected AC adapter.
The cable length between MultiSensor and the KIO3 adapter should not exceed 10m.
The relays are equipped with PDT contacts and can be loaded with up to 60VDC/3A.
Figure 1: Back of Kentix Power-Adapter (KIO3)
Figure 2: Circuit diagram
"
Important!
When using the input clips for external alarms and simultaneous power supply of two MultiSensors remove
the jumpers. Otherwise the external alarms will be indicated on both sensors.
Commentaires sur ces manuels