External I/Os of MultiSensors
Examples of external circuits of the MultiSensors. This shows the internal 8-pin terminal of the MultiSensor.
The internal circuit of inputs and outputs is shown schematically for better understanding. The logic of the
alarm inputs can be rotated in the ControlCenter. Running in standalone mode, this is also possible via the
MultiSensor-LANs web interface.
Example: Wired connection with power supply via internal terminal.
IMPORTANT!
The switching outputs 6/7 are open collector transistor outputs and the maximum load is 100mA.
For plug´n play use of the outputs you can choose KENTIX module: KIO1 Power-Adapter
The switching output 6 in standalone mode can only be activated via the SNMP or SMS remote function.
In AlarmManager mode the output can be used for arm/disarm signalization.
The switching output 7 is automatically switched by an alarm (Armed-Active or Always-Active) trigger.
The alarm inputs 2/3 can be directly connected with potential-free contacts.
When using the system jack for power supply you can switch the alarm inputs 6/7 direct to the pin 8 (GND)
of the internal 8-pin terminal. See also example 2 for the MultiSensor.