Overview connections
Network-Port
Kentix System-jack 1
Kentix System-jack 2
OLED Display
Display scroll forward
Display scroll back
System state
Reset-Button
PDU-1 (Main PDU)
Independent of PDU-2
Max. power consumption 3.600VA
Internal protection 2x10A, time lag fuse
Total load over all 4 outputs max. 16A
Power Strip switchable
Energy measurement outlet 1-4
Main equipment supply - Electronics
PDU-2
Independent of PDU-1
Max. power consumption 3.600VA
Internal protection 2x10A, time lag fuse
Total load over all 4 outputs max. 16A
Power Strip switchable
Energy measurement outlet 1-4
PDU-1
UPS-Mains connection
(Type C20)
PDU-1, Output 1
Power outlet 1+2
(Type C13, 2.300VA/10A)
PDU-2
UPS-Mains connection
(Type C20)
PDU-2, Output 2
Power outlet 3+4
(Type C13, 2.300VA/10A)
PDU-1, Output 2
Power outlet 3+4
(Type C13, 2.300VA/10A)
PDU-2, Output 1
Power outlet 1+2
(Type C13, 2.300VA/10A)
Recommended installation
Installation to front or back
support rail
Page 37 ! ! ! ! (08-2014, subject to change) kentix.de