Enhancements
With the Alarm inputs at the terminal blocks or the system jacks of AlarmManager and MultiSensor it is
possible to connect external components like door-contacts or leakage-sensors.
In the following you see connection examples for the leakage-sensor available at Kentix.
Leakage-sensor
The leakage-sensor is already prepared with a RJ45-connector for Kentix devices.
Powering is also realized via this connector. A LED inside its case signals the actual state of the sensor
(green: no alert / no humidity; red: alert / humidity detected). To test functionality, touch the bottom of the
sensor with a slightly wetted cloth).
Connection example 1: Leakage-Sensor connected to AlarmManager
Plug the connection cable of the leakage-sensor into one of the System-jacks of the AlarmManager.
The powering and alarming is done directly via the AlarmManager. With the ControlCenter enter a suitable
name for the external alarm input and set the alarming of the input to „Always-Active“ for a permanent
alarming. If the leakage sensor is working with opening the contact on an alarm, additionally change the
alarm logic to „Open“.
IMPORTANT!
The signaling for a connected leakage-sensor is realized via the external alarm input of the device to which
the leakage-sensor is connected (AlarmManager or MultiSensor). For the correct functioning, this input has
to be configured correctly (see examples).
Therefor its necessary to test the alert triggering after connection to ensure the correct cabling.
AlarmManager-BASIC/PRO
Leakage-sensor
KENTIX System-jack
Page 51 ! ! ! ! (08-2014, subject to change) kentix.de